Whatever Type of Water Chiller,
TopChiller Can Fulfill the Water Chiller Solution for You.

  • 20 years of water chiller manufacturing experience: TopChiller is a leader in water chiller manufacture with rich experience
  • 18 month warranty time: TopChiller provide an 18-month warranty for standard water chillers that can extend to 24 months covered all water chillers
  • Famous brand spare parts: Each water chiller from TopChiller uses world-famous brand refrigeration spare parts
  • Technical support& Training service: TopChiller can provide all clients water chiller installation and commission service
  • 8 Hours troubleshooting: In case of any water chiller error or alarm, TopChiller will give a quick response within 8 hours to solve your water chiller problem
  • Lifetime service: TopChiller promise clients to give all water chiller whole lifetime service free of charge
  • Water Chiller

Why TopChiller Can Be Your Reliable Water Chiller Manufacturer and Supplier

20 Years Water Chiller Manufacturing Experience
TopChiller is a leader of water chiller manufacturers with rich experience.
24 Months Warranty Time
TopChiller provides extend to 24 months of warranty time covering all water chillers.
Famous Brand Water Chiller Spare Parts
Each water chiller unit from TopChiller uses famous brand spare parts.
Technical Support & Training Service
TopChiller can provide water chiller installation and commission service.
8 Hours Chiller Troubleshooting
In case of any water chiller error, TopChiller gives a quick response within 8 Hours
Whole Life Time Service of Your Water Chiller
TopChiller promise to give all water chiller unit a whole lifetime of service

Water Chiller: Your Premier Choice
Of Industrial Chillers

A water chiller is also called a water-cooled chiller or water-to-water chiller and water cooling chiller.

A water chiller is a mechanical device that can produce cold and chilled recirculating water for various industrial applications use.

TopChiller® is your professional water chiller supplier and company with over 20 years of experience.

Water chiller designed and manufactured from TopChiller® equipped with USA Copeland brand, France Danfoss brand, and Japan Sanyo brand hermetic scroll compressors, have spare parts available from the world-famous refrigeration brands.

This water chiller from TopChiller company features a water-cooled shell & tube type condenser, stainless steel water tank heat exchanger as the evaporator, but shell & tube or stainless plate type heat exchanger option based on detailed requirements.

But compared with an air chiller, a water chiller needs to install a proper cooling tower and cooling pump to work together.

This is the biggest difference between a water chiller and an air chiller.

Each water chiller unit before delivery is charged with environmentally friendly refrigerant R407c, with R134a, R404a, and R410a, also available for different industrial applications and ambient temperature demands.

A high-quality water chiller designed and manufactured by TopChiller features some outstanding advantages as below:

1. Environmental friendly – TopChiller water chillers are charged with HFC-R410A, R407c, and R134a refrigerants, which have no ozone-depletion potential and no phase-out schedule.

2. High Efficiency – Water chillers made from TopChiller are leading design and off-design efficiencies.

3. Compact Design – All water chillers are designed with a compact structure for ease of installation.

4. Reduced wiring costs –Our water chillers are with Lowest MCAs in the industry and also maximize capacity on retrofit projects.

5. Low Operating Costs – TopChiller water chiller with rugged design for low maintenance costs and long design life.
As a leader of a water chiller manufacturer, TopChiller has a complete product range of water chillers including portable water chiller, recirculating water chiller, screw chiller, and other industrial water chillers.

All these water chillers are the best industrial cooling partner for your machines.

With the capacity to meet cooling requirements for a wide range of commercial and industrial facilities, get the performance you want from your cooling equipment with a water chiller from TopChiller now.
For decades years, TopChiller has exported thousands of high-quality water chillers throughout world countries.

The cooling capacity is from small 5ton, 10ton,15ton, 20ton, 25ton,30ton to middle size 40ton,50ton,60ton, and up to 100ton,120ton, 15t0n.

Our water chiller customers are the Philippines, Australia, New Zealand, Malaysia, Singapore, Indonesia, Chile, Mexico, Costa Rica, Brazil, Argentina, Colombia, South Africa, Nigeria, Saudi Arabia, Dubai, Spain, Italy, etc.

If you are looking for a high-quality water chiller supplier?

If you need a long-lasting water chiller for cooling your machine or plant process?

You are coming to the right water chiller factory.

As a professional water chiller manufacturer with rich experience in refrigeration, we have enough confidence to satisfy your special requirement on any water chiller needs.

Please do not hesitate to contact TopChiller sales to get the best price for your water chiller.

Read More

General Description:

Water Chiller is a compact footprint cooling device that works on refrigeration and discharges heat by chilled water circulation. It provides a chilled water supply through its internal pumping system for application cooling. At the same time, the heat is discarded by an air/water-cooled condenser.

Water Chiller manufactured by TopChiller is featured with innovative design components for reliable operation as temperature controller, internal reservoir, and water regulating valves, condenser fans, condenser, heat exchanger, expansion valves, scroll compressor, electric current components, and high/low-pressure switches.

TopChiller designed Water Chiller is preferably used for applications requiring cooling solutions such as MRI machines, laser industry, die-casting, injection moulding, blow moulding, hotels, hospitals, laboratories, pharmaceuticals, welding, metalwork, etc.

TopChiller is a thriving manufacturer and supplier of the global world focused on offering flexible designed and customer-oriented Water Chiller. With productive work experience, we can make recommendations and amendments in Water Cooling Systems for customer needs.

Are you in quest of a reliable Water Chiller for quick temperature regulation of your processing machines? You need to contact a world fabulous enterprise, TopChiller.

So make an email or call our sales engineers and finalize your order at relatable charges. All Water Cooling Systems are quality enlisted with endless options of customization.

TopChiller can design customized Water Chiller according to your requirements and budget.

Features and Advantages:

Water Chiller designed by TopChiller is fabricated with standardized features offering the best performance and a diverse number of benefits as given below:

  • Chilled water is supplied continuously to flow over the processing machine. The water coolant quickly absorbs the system heat for temperature maintenance mediated by the water pumping system and reservoir.

 

  • The unit is made redundant and configured by installing a dual refrigeration circuit and compressor, assuring operation continuity in case of damage in one circuit.

 

  • No direct contact with environmental factors and the quick heat absorption feature of water from the processing unit makes the Water Chiller durable with long service life.

 

  • Stainless steel brazed plate evaporator consists of convoluted tubing engraved in plates. It provides a site for heat exchange between coolant and refrigerant. The evaporated refrigerant is dislocated from the evaporator to the condenser for heat expel.

 

  • The whole unit is made-up of corrosion-resistant stainless steel material. Except from, pipes for water circulation are also made corrosion protective. Access towards the internal components is made possible by the side opening panels.

Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler- Water Cooled Chiiler-

Water Chiller Technical Specifications

Water Chiller

TopChiller: Your Leading Water Chiller Manufacturer and Supplier in China

TopChiller is a professional water chiller manufacturing company with 20 years of experience.

Compared with an air chiller, a water chiller should connect the circulation water pump and install an external water cooling tower as the heat exchanger for reliable working conditions, performance, and high cooling efficiency.

This water chiller manufactured by the TopChiller team is your reliable water cooling partner, can be widely used for a plastic injection molding machine, blow molding machine, plastic extruder, chemical industry, and many other applications.

A water chiller provides a constant chilled water flow rate to improve the development process and increase productivity.

As a leader in the water chiller field, all water chillers made by TopChiller® are 100% tested and well packaged before delivery to make sure they are in perfect working conditions.

Each water chiller designed and manufactured by TopChiller has 12 months regular warranty time that covers the whole water chiller unit and all refrigeration spare parts.

 

As the most professional water chiller supplier with 20 years of experience, TopChiller® would like to give perfect water chiller solutions at competitive prices.

Please contact our engineering team to customize your water chiller solution for your business.

TopChiller is sure about your special water chiller requirements will be satisfied with our engineering department.

Water Chiller Fabricated by TopChiller

Water Chiller Fabricated by TopChiller

A Complete Buy Guide of Water Chiller from TopChiller

Chapter 1: What is a water chiller

In the refrigeration industry, water chillers can be divided into air-cooled chillers and water-cooled chillers.

According to the compressor types, a water chiller is divided into a screw water chiller and a scroll water chiller.

A water chiller is a kind of water cooling equipment, which can provide constant temperature, constant current, and constant pressure for your applications.

The water chiller offered by TopChiller ranges from 2 Ton to 60 Ton in cooling capacity and the chilled water flow rate is up to 680 LPM.

Cooling water temperature can be adjusted automatically according to the requirements, the temperature controlling the range of water chiller by TopChiller is from 7℃ to 35℃,and water can be saved by long-term use.

Therefore, a water chiller is a kind of standard energy-saving equipment because it can save your water and cost.

More generally, you can always output chilled water with a lower temperature than the environment.

You can use it whenever you need to cool down. It can be cooled directly or by heat exchanged indirectly.

The water chiller consists of four main components: compressor, evaporator, condenser, expansion valve, to achieve the cooling effect.

In the industrial field, a water chiller is one of the most commonly used refrigeration equipment. Water Chiller plays an important role in industrial refrigeration.

Many water chillers are controlled by microcomputers, which are easy to operate, have high precision, have a wide range of use, and can accurately control water temperature.

At the same time, the perfect electrical protection system has the protection of phase absence, phase staggering, current overload, high and low voltage, compressor exhaust overheating, etc. to ensure the efficient operation of your water chillers.

Chapter 2: How does a water chiller work

The operation of the water chiller system is accomplished by three interrelated systems:

Water chiller refrigerant-cycle system, water cycle system, and electrical automatic control system.

water chiller working diagram

Water Chiller Working Diagram

2.1 Water chiller refrigerant cycle system:

Let’s have a brief introduction to the water chiller refrigerant cycle system.

The liquid refrigerant in the evaporator absorbs the heat in the water and starts evaporating. It becomes gaseous and then is inhaled and compressed by the compressor (pressure and temperature increase), and then transported to the condenser.

The high-temperature pressure gaseous refrigerant releases heat through the condenser (water-cooled), condenses into liquid, and becomes a low-temperature and low-pressure refrigerant after saving pressure by the thermal expansion valve (or capillary tube).

After entering the evaporator to absorb heat in water, a cycle process of refrigerant was completed. Refrigerants circulate in such a way that they constantly take heat away from the water and then reach the intent of cooling water.

Water chiller refrigerant cycle system

Water Chiller Refrigerant Cycle System

2.2 Fundamental  composition of your water chiller

2.2.1 Compressor

The compressor is the core component of all water chillers, and also the power source of refrigerant compaction.

Its effect is to convert the input electric energy into mechanical energy and tighten the refrigerant.

2.2.2 Condenser

The condenser of a water chiller acts to output thermal energy and condenses the refrigerant during the cooling process.

After the high-pressure superheated vapor discharged from the refrigeration compressor enters the condenser.

it absorbs all the heat in the operation process, including the heat absorbed from the evaporator and the refrigeration compressor and in the pipeline, which is transferred to the surrounding medium (water or air); the high-pressure superheated vapor of the refrigerant condenses into liquid again.

2.2.3 Liquid reservoir

After the condenser, the Liquid reservoir device is directly connected with the discharge pipe of the condenser.

The refrigerant liquid of the condenser should flow into the reservoir in all directions so that the cooling area of the condenser can be fully utilized.

On the other hand, when the heat load of transpiration changes, the requirement of refrigerant liquid also changes.

At that time, the reservoir will play the role of adjusting and storing refrigerants.

Regarding the small refrigeration equipment system, the condenser is usually used to adjust and store refrigerants instead of the liquid reservoir.

2.2.4 Dryer filter

A dryer filter is another important part of a water chiller.

It is necessary to prevent moisture and dirt (oil, iron, copper) from entering the refrigeration cycle.

The origin of moisture is mainly the trace moisture contained in the newly added refrigerant and lubricating oil or the moisture brought by the air entering into the maintenance system.

If the water in the system is not cleaned, when the refrigerant passes through the saving valve (thermal expansion valve or capillary).

Sometimes the water will condense into ice due to the decrease of pressure and temperature, which will block the passage and affect the normal operation of refrigeration equipment.

2.2.5 Thermal expansion valve:

In a water chiller, the thermal expansion valve is a must refrigeration part.

The thermal expansion valve is not only a flow regulating valve in a refrigeration system, but also a saving valve in refrigeration equipment.

It is installed between the dry filter and evaporator in refrigeration equipment, and its temperature sensor is wrapped at the outlet of the evaporator.

Its primary effect is to make the refrigerant liquid at high pressure and normal temperature save pressure when flowing through the thermal expansion valve, and turn into low temperature and low-pressure refrigerant wet vapor (some are liquid, some are steam) into the evaporator, vaporize and absorb heat in the evaporator, and reach the intention of cooling.

2.2.6 Evaporator

Besides the above, the evaporator is another important heat exchanger for your water chiller.

The evaporator is a heat exchanger which absorbs the heat of the cooling medium by the transpiration of refrigerant liquid (actually boiling).

The evaporator of the water chiller functions in the refrigeration system is to absorb heat (or output cooling).

To ensure that the transpiration process can proceed steadily and be durable, it is necessary to constantly use a refrigeration compressor to extract transpiration gas, to maintain a certain transpiration pressure.

Most water chillers used in the modern industry use refrigerants R22 or R134a and R407c, Refrigerants are active refrigerants in refrigeration systems.

Their primary effect is to carry heat and to achieve heat absorption and release when conditions change.

2.3 The water circulation system

In this part, we will know something about the water circulation in a water chiller.

The water circulation system is a pump that draws water from the water tank to the equipment that the user needs to cool.

After the heat is taken away by the chilled water from the water chiller, the temperature increases and then returns to the chilled water tank.

Water Chiller compressor

Water Chiller Compressor

Chapter 3: The difference between Water chiller and Air chiller

To know more information about water chiller, firstly we should tell apart the difference between water chiller and air chiller.

The air chiller realizes the refrigeration function by refrigeration cycle cooling water of the chiller.

Because of the heat exchange between the fan and the air, therefore, air-cooled water chillers also use a fan, dust-proof net, and other heat dissipation components to carry out heat dissipation.

Air chiller can control temperature while maintaining stable performance, occupying small space, easy to move, easy to operate.

The water chiller cools the circulating water through the chiller’s refrigeration system and then delivers it to the equipment through the pump and the cooling water route.

The water chiller is relatively less affected by the environment, but the company needs a good quality water source for circulation cooling.

Due to the water tower, the water chiller occupies a large area, and the installation and maintenance workload is large.

The following are specific differences between the water chiller and the air chiller.

3.1 Cost

Because the heat exchange efficiency of water is much greater than the air exchange efficiency, the water chiller is more energy-efficient than the air chiller.

Compared with the water-cooled condenser with the same heat transfer capacity, the air-cooled condenser has a larger volume, more materials, and higher manufacturing costs.

The total cost of water chillers is still 15-20% lower than that of internal chillers even if the equipment cost of the cooling water system is added.

In addition, because the nominal power of the air chiller unit is larger than the nominal power of the water chiller unit, the cost in terms of power capacity increase and electronic control equipment is also high.

So if you require a big cooling capacity, you should go for a water chiller than an air chiller.

air chiller vs water chiller on cost

3.2 Performance

The heat transfer temperature difference of the water chiller condenser is generally 4℃-8℃, while the air chiller has a heat transfer temperature difference of generally 8℃-15℃ in the same outdoor ambient temperature.

The temperature of the cooling circulating the water is lower than the outdoor air temperature, so the condensing temperature of the air chiller unit in normal operation is much higher than the condensing temperature of the water chiller unit.

So that the air] chiller unit consumes more power in refrigeration than the water chiller unit under the same cooling capacity.

air chiller vs water chiller on performance

3.3 Installation room

For water chillers, these chillers’ installation rooms should be provided to ensure that the normal operation and service life of equipment including water chillers and chilled water circulating pumps, and cooling tower equipment should be placed on the roof or outdoor floor of buildings.

It can be seen that, in the case that the building cannot provide enough room, the selection of air-cooled chillers should be a better way.

3.4 Operation cost

Because the water chiller operates at a lower condensing temperature, the refrigeration efficiency is high and the power consumption of the unit is small.

Generally speaking, compared with an air chiller with the same refrigeration capacity, the overall power consumption of the water chiller is about 25% lower than that of air-cooled units (including the power consumption of cooling water pumps and cooling tower fans).

3.5 Regular Maintenance

Shell-and-tube condensers used in water chillers have a low impact on heat transfer efficiency within a certain range of fouling accumulation, so the performance of water chiller units decreases slightly with fouling generation, and the cleaning cycle is longer.

The heat transfer efficiency of the finned condenser used in air chillers is greatly affected by the accumulation of dust.

The dust grids must be set before the fin tubes for heat dissipation, and frequent cleaning is required.

Because of the high operating pressure of air chiller units, they are usually installed outdoors, and the operating environment is relatively harsh.

Air chillers are inferior to water chillers in terms of maintenance and reliability.

Some tips for water chiller maintenance

1. Do not shut down the water chiller by cutting off the main power supply in case of an emergency.

2. When the water chiller fails to alarm and stop, first turn off the main power switch of the machine (the alarm lamp will be extinguished), and then check the cause of the failure.

The water chiller must not be forced to start before the failure is eliminated.

3. To prolong the water chiller life of the system and prevent the occurrence of safety accidents, a regular inspection must be carried out.

4. The water quality of the system should be treated. The high alkaline water quality will aggravate the corrosion of copper tubes and reduce the service life of heat exchangers.

The PH value of the water used is in the range of 7.0-8.5. 5. Keep the room dry, clean, and well ventilated.

5. The daily operation, management, and maintenance of your water chillers must be carried out by people with professional skills.

(It is dangerous to disassemble or inspect the water chiller unit when your water chiller is running, please note!)

6. Refrigerant gas leakage happened with a water chiller, If this problem happens, we should recharge some refrigerant.

Please follow the below sequence:

Filling Refrigerant:

Turn off the lid of the valve and connect the air pipe of the vacuum pump to the valve for vacuum pumping. The process takes about 1 to 3 hours.

After the vacuum is exhausted, the gas pipe of the refrigerant tank is connected to the needle valve, and the refrigerant is added to the return pipe.

Monitor the change of electronic weighing and stop filling refrigerant when filling rated weight. (No liquid refrigerant in startup state) startup

Under the condition, the pressure of the high-pressure gauge is about 13-15 bars, and the pressure of the low-pressure gauge is about 3-5 bars.

Water-cooled chillers use shell-and-shell condensers, which accumulate scales on the inner side of heat transfer tubes for a long time, which affects their heat transfer effect.

The condensers should be cleaned regularly to keep your water chillers working well.

If the cooling water has been treated as water purification, it is suggested to sterilize and remove algae with hydrogen peroxide, rinse ears with a high-pressure water gun, and then check whether there is a scale.

Passivation is necessary after pickling. Passivation can be purchased for relevant treatment.

When the water chiller stops in the environment below 0 ℃ and is not used or stored, the pipeline should be disconnected, the front end of the water chiller should be improved.

And the water wrapped in the ice condenser should be discharged strongly and nearly as cold as that wrapped in the ice condenser.

A Shell-and-tube evaporator is used in the water chiller. Scale accumulates on the outside of the heat transfer pipe for a long time, which affects its heat transfer effect.

Regularly clean the evaporator to keep your water chiller good working performance. The evaporator is cleaned by cleaning the frost condenser. The scale is discharged from the drain.

Chapter 4: Water Chiller Industrial Applications

In most industrial applications, water chillers are used in a variety of industries to control products, mechanisms, and plant machinery cooling.

Water chillers are commonly used for injection and blow molding in the plastic industry, metalworking cutting oils, welding equipment, die casting and machining, chemical processing, food and beverage processing, paper making, cement processing, vacuum systems, X-ray medical equipment, and power stations, analytical equipment, semiconductors, compressed air, and gas cooling.

Water chillers are also used to cool high-heat energy, such as nuclear magnetic resonance imaging and laser-specific engineering projects, and in hospitals, hotels and campuses.

Plastics industry: water chillers precisely control the mold temperature of various plastic processing, shorten the beer-plastic cycle, and ensure the stability of product quality.

Sometimes water chillers are used to cool down your finished plastic products.

Electronics industry: water chillers stabilize the molecular structure of electronic components in the production line, improve the qualified rate of electronic components, apply to the ultrasonic cleaning profession, and effectively avoid the damage caused by evaporation of precious detergents.

Electroplating industry: water chillers control the plating temperature, increase the density and smoothness of the plated parts, shorten the plating cycle, improve the output power, and improve product quality.

Machinery industry: water chillers control the pressure oil temperature of the oil pressure system, stabilize the oil temperature and oil pressure, extend the oil quality application time, improve the mechanical smooth power, and reduce wear.

Construction industry: water chillers provide chilled water for concrete, make concrete molecule structures suitable for building use requests, and effectively enhance the hardness and durability of concrete.

Vacuum coating: water chillers control the temperature of the vacuum coating machine to ensure the high quality of the plated parts.

Food industry: water chillers are used for high-speed cooling after food processing to make it accustomed to packaging requests. Others include controlling the temperature of fermented food.

Besides the above industrial applications, water chillers can be also served some specific industries.

Please contact the TopChiller water chiller expert to customize your water chiller.

Chapter 5 Why TopChiller can be your reliable Water Chiller supplier?

TopChiller, as the world’s leading water chiller manufacturer, produces more than 5000 water chiller units annually and provides high-quality water chillers as our goal.

Here are some reasons why TopChiller can be your reliable Water Chiller supplier

5.1 Rich experience in water chiller and professional service team

Since TopChiller was established in 1999, we have been accumulating experience in the field of water chillers to provide high-quality water chillers to customers around the world.

We have a skilled team that is ready for providing all technical support all the time if you have any water chiller problems.

5.2 Using water chiller spare parts of internationally renowned brands

To ensure the high quality of water chillers, TopChiller uses internationally advanced compressors, such as USA Copeland, France Danfoss or Japan Sanyo, Germany Bitzer, and Taiwan Hanbell.

We are also strict to control over every part, water pumps and condensers in water chillers can be configured according to specific requirements.

5.4 Extremely testing of all water chiller units before delivery to the customer

All water chillers will be strictly tested before delivery to clients.

Let’s have a look at the water chiller air tightness inspection, with experimental procedures and vacuum test indicators.

The water chiller has completed the airtight test before leaving the factory and is filled with 0.03 ~ 0.05MPa nitrogen for protection.

The site is determined by the following method to see if the unit is leaking. If it is not leaked, it can be avoided as a gas-tight test.

1)the pressure inside the water chiller is 0MPa or the pressure is lower than 0.03MPa, and it is determined that the water chiller unit has leaked;

2) After charging the water chiller, the water chiller unit is filled with refrigerant and leaked with a leak detector or an electronic leak detector.

When the water chiller finds a leak during the inspection, the airtight test shall be carried out according to the following procedure:

  1.  Prepare nitrogen, add gas pipe and pressure reducing valve. Fill the water chiller with nitrogen gas. When the pressure is 0.6~0.7MPa, close the intake valve and check the leak with the leak detection fluid to check all the leak points.
  2.  Mark the leak point, find out the cause, and make up the leak after the pressure is zero.
  3.  After the completion, re-boost and check again. Do not pressurize the leak.
  4. nitrogen is boosted to the water chiller design pressure 1.28MPa, and the leak point is checked and treated.
  5.  Pressure relief
  6. When it is confirmed that the water chiller has no leakage, the nitrogen in the water chiller unit is discharged. When the pressure is discharged at 0.3 MPa, the evaporator pressure transmitter valve is closed and the discharge is continued to zero.

After the water chiller airtight test is passed, the vacuum test is carried out.

The vacuum test process is as follows:

  1. connect the vacuum gauge to the water chiller.
  2. Connect the vacuum pump to the refrigerant charging valve of the water chiller, and require the pump to the unit to be as short as possible and the diameter as large as possible to reduce the airflow resistance.
  3.  Open all internal shut-off valves of your water chiller.
  4. Evacuate to an absolute pressure of 500Pa or less (the factory requires an absolute pressure of 200Pa or less). Hold pressure for 2 hours, and the recovery is ≤200Pa (factory requirement ≤100Pa) is qualified. If the recovery is ≥200Pa (factory requirement ≥100Pa), it means that the unit has a leak point or the humidity inside the unit is too large. At this time, it should continue to vacuum for more than 2 hours to re-pressurize.
  5. After being repeated several times, the water chiller is still unqualified, and the airtight test is re-tested and trapped.

Note: When adding fluorine, the vacuum of the water chiller should not exceed the absolute pressure of 500Pa.

5.3 Pre-sales and After-sales Service

Our sales and technical team provide you with free support throughout the day, providing the most professional and just-in-time technical consults and water chiller solutions for you.

When we get your water chiller inquiries, we will reply to you within 5 hours, 24-month warranty is provided for our products, and contact us at any time during the chiller’s whole lifetime service

 

Chapter 6: How to size a suitable water chiller for your machine

A water chiller is a kind of refrigeration equipment that can provide chilled water for all industries to achieve the purpose of cooling.

It can control the temperature between 5 degrees and 35 degrees, and the low-temperature water chiller can control the temperature between 0℃ to -40℃.

In the selection of water chillers, we need to know exactly how much the inlet and outlet temperatures of chillers are, how much the flow rate is, and how big the water tank is.

A water chiller with high quality is the guarantee of successful engineering design and has a long-term impact on the operation of the system.

Cooling water flows: refers to the cooling circulating water flow of the chiller that needs to be supplied when refrigerating equipment is used.

Cooling capacity: that is, how much refrigeration capacity is needed? The commonly used units of refrigeration capacity are Kcal/h, kw, etc.

Outlet-water temperature: return-water temperature or temperature difference between outlet-water and return-water: Outlet-water temperature refers to the temperature of chilled water, and return-water temperature refers to the temperature of cooling water.

Some equipment with stricter heat dissipation requirements will have the temperature requirement of a cooling water supply.

Outlet-water pressure: Because of the complex internal heat dissipation structure of some heat dissipation equipment, there is a certain pressure requirement for cooling water supply.

At this time, it is necessary to consider whether the rated outlet water pressure of the water chiller can meet this requirement.

Pump lift: If a single water chiller is used one-to-one, the pump lift should not be a problem.

If multiple water chillers are connected in parallel for the application of multiple cooling types of equipment, the resistance of the pipeline system should be taken into account, to calculate how many pump lifts need to be allocated.

Control adjustment requirements: generally refers to pressure control adjustment and temperature control adjustment.

Safety protection function requirements of water chillers:

A. Compressor delay starts protector

B. High and low voltage protection function

C. Inverse phase protection

D. Compressor overload protection

E. Antifreeze protection

F. Compressor overheats protection

G. Compressor frequent start protector and abnormal indicator lights and various protection switches.

Chapter 7: Water Chiller Installation Guide

Installation of water chillers (mainly is basic vibration isolation equipment): We are well aware that the installation of equipment must choose a flat and open place, chillers are no exception.

Before installing water chillers, many users will do a good job of foundation preparation and embedding four horizontal pad iron in advance.

Generally, the water chiller has four legs, which can be equipped with an adjusting padding plate with two adjusting threaded holes to adjust the level of the whole water chiller, and use concrete mortar to fill in the gap after adjustment.

After the mortar is dried, the adjusting bolt can be removed, the positioning bolt can be left behind, and fixing measures can be taken for the water chiller.

Installation of water chiller pipes: mainly are the external water pipes of evaporator and condenser, if it is double-return water pipes, it is arranged on the same side.

If it is single-return or three-return water pipes, it is arranged on both sides, The inlet and outlet water of water chillers’ condenser and evaporator are from bottom to top.

Note:

water chiller water pipe cleaning: After installing the water pipe to the unit, the whole water system should be tested for leakage. After the leakage test is qualified, the water pipe can be cleaned.

When cleaning water pipes, we should first make sure the direction of the pump is correct. and open all the valves of the inlet and outlet pipes.

The pipes are full of water, start the chilled water pump and the cooling water pump, run continuously for two hours, stop the operation of the pump, drain all the cold water and cooling water, and clean the pump filters.

Chapter 8: Troubleshooting of  Water Chiller

Each water chiller not only completes comprehensive performance testing before leaving the factory but also equips the unit with various safety protection devices,

such as phase protection, low water level protection, water flow switch protection, pump overload protection, compressor overload protection, high and low voltage protection, etc.,

to avoid secondary damage caused by the failure of your water chiller unit. When the unit fails to occur, the corresponding protection device will give a warning and stop the water chiller operation.

Trouble-shooting method: If the water chiller is used too long or not maintained regularly, some unexpected faults will inevitably occur. Here are some common troubleshooting methods.

8.1. Inverse phase

When your water chiller fails, it will be timely phase protection. The cause of the reverse phase is a reversal of the pump and compressor.

At this time, we can switch any two phases in the power supply phase line.

If the phase is absent, we only need to measure whether the three-phase power supply is normal with a multimeter to check whether the power supply line is broken.

8.2. The refrigerant is not enough and the indicator light is on

A. When the water temperature is above 5 °C when the pressure of the low-pressure gauge is less than 2 kg/cm2, it means that the refrigerant is insufficient.

First, the place where the refrigerant is leaked is subjected to trapping treatment, and then the dry filter is replaced and the vacuum is refilled to fill the appropriate refrigerant.

B. When it is found that the leaking refrigerant is partially immersed in water, stop the operation of the water chiller immediately, remove the water in the water tank quickly, and handle the repair as soon as possible to prevent the compressor from inhaling water into the system and causing more serious damage.

8.3. Poor heat dissipation results in slow or non-refrigeration

When the condenser heat dissipation is poor, the compressor efficiency is low and the running current is increased.

When the air-cooled high pressure rises to 24kg/cm2, the water-cooled high pressure rises to 20kg/cm2, and the compressor is subjected to high pressure.

The switch protection trips, the compressor stops running, the heat dissipation is poor, the high voltage is overloaded and the fault code or fault indication is displayed.

At this time, please check whether the cooling tower circulating the water is normal, whether the cooling water temperature is too high, whether the cooling tower fan water pump is running, and whether the cooling water valve is running.

The above is normal, press the reset button or shut down and restart to running normally.

If high voltage overload occurs frequently, please arrange to clean the condenser as soon as possible.

8.4. Whether high and low pressure is normal

The second and third of the previous ones analyze in detail the pressure display of the compressor when the high pressure or the low pressure is abnormal.

Then when the compressor runs, the difference between high pressure and low pressure is small or equal, the compressor fails.

then we should check whether the value of the compressor itself is damaged or broken, and immediately stop running and notify the supplier to send someone to deal with it.

If you have any questions in troubleshooting, please contact the sales engineer of TopChiller, we are very glad to help you solve those problems

8.5. Treatment of the insufficient refrigerant or refrigerant leakage

1. Fault phenomenon:

The cooling effect of the whole water chiller is poor, the outlet is only cool, and the pressure on the high-pressure side and the low-pressure side is low by the manifold pressure gauge.

(At the normal speed of the compressor, when the ambient temperature is about 35 °C, the low-pressure gauge index is lower than 1 kg. /cm2, the high-pressure gauge index is lower than 10kg/cm2), and the bubble flow is visible from the sight glass.

2. the cause or reason of the failure:

water chillers have refrigerant leaks that result in insufficient refrigerant.

3. Processing method:

1) Use an electronic leak detector to detect leaks and repair or replace parts.

2) If the parts are not replaced, only the appropriate amount of refrigerant can be replenished; if the parts are replaced, the appropriate amount of refrigerating oil should be added as required, and the refrigerant should be added after the system is vacuumed.

8.6 Excessive refrigerant charged

1. Fault phenomenon:

The water chiller cooling effect is poor. When checking with the manifold pressure gauge, the pressure on the high-pressure side and the low-pressure side is too high (when the compressor speed is normal, the ambient temperature is 35 °C, the pressure of the high-pressure gauge is about 19 kg/cm2, and the pressure of the low-pressure gauge is 2.3. Kg/cm2 and no bubble flow is seen in the liquid mirror.

2. the cause of the failure:

Too much refrigerant is added to the water chiller, so that the refrigeration capacity cannot be fully utilized, resulting in poor cooling performance.

3. Processing method:

Connect the manifold pressure gauge in the system, and slowly loosen the low-pressure side manual valve of the manifold pressure gauge to make the refrigerant discharge slowly (can not be discharged from the high-pressure side.

Because the refrigerant will bring out a large amount of frozen oil from the high-pressure side).

Until the high and low side pressure is normal, at the same time, the clear flow of the refrigerant can be seen from the sight glass, and occasionally bubbles flow.

8.7  Refrigeration system mixed with air

1. Fault phenomenon:

The water chiller refrigeration capacity of the whole machine is reduced.

when the manifold pressure gauge is used, it is found that the high-pressure side pressure is high, and the low-pressure side pressure is sometimes higher than the normal value.

When the compressor speed is normal, the ambient temperature is 35 °C, the high-pressure side pressure Above 20kg/cm2; and the high-pressure gauge pointer has a swing;

on the other hand, many bubble flows can be seen from the sight glass.

2. the cause of the failure:

Air is mixed into the water chiller system.

Mainly after the assembly or overhaul, the vacuum is not complete; when charging the refrigerant or adding the frozen oil, bring the air into the system, or when the system is working under negative pressure, the air is mixed through the tight place.

After the air enters the refrigerant, it has a certain pressure, and the refrigerant also has a certain pressure.

In a closed container, the total gas pressure is equal to the sum of the partial pressures, so the high and low-pressure meter readings are higher than the normal value.

3. Processing method:

1) Release the refrigerant (discharged from the low-pressure side with a pressure gauge).

2) Check the cleanliness of the compressor oil.

3) Refill the refrigerant after vacuuming.

8.8 “Ice blockage” in the refrigeration system

1. Fault phenomenon:

The refrigeration system periodically cools down and then does not cool.

During operation, the pointer on the low-pressure side of the manifold pressure gauge often fluctuates between the negative pressure and the normal value.

2. the cause of the failure:

The refrigerant in the refrigeration system is mixed with water.

Since the moisture is incompatible with the refrigerant, when the refrigerant flows through the orifice of the expansion valve, the temperature suddenly drops, and the moisture mixed in the refrigerant is easily ice particles in the vicinity of the orifice of the throttle valve or near the hole of the valve pin are spherical or hemispherical.

When the ice particles are knotted to a certain extent, the throttle channel is blocked and an ice blockage is formed.

When the ice is blocked by ice, the refrigeration system can not work normally, and the cooling effect is reduced, even without cooling.

At this time, the negative pressure occurs in the low-pressure gauge, so the temperature of the ice block rises remarkably, the ice particles blocked by the ice melt into water.

The ice blockage phenomenon disappears, the refrigeration system resumes normal operation, the refrigeration is good, and the low-pressure side pressure returns to normal.

After a while, the system blocked ice again and the system was not working properly.

3. Processing method:

1) Since the desiccant is in a supersaturated state, the reservoir with the desiccant must be replaced and 30 ml of frozen oil is added.

2) Vacuum the system and add a specified amount of refrigerant.

8.9 Dirty block troubleshooting

1. Fault phenomenon:

Poor cooling or no cooling.

When the water chiller is running, the readings of the high/low-pressure gauges on the manifold pressure gauge are all less than the normal values.

When the compressor speed is normal, the ambient temperature is about 35 °C, the pressure on the high-pressure gauge side is lower than 9 kg/cm2, and the pressure on the low-pressure side is at a Negative pressure state), and there is frost or condensation on the pipeline before and after the filter and capillary.

2. the cause of the failure:

In the water chiller, dust adheres to or adheres to the filter at the inlet end of the filter, or the interface between the capillary and the filter makes a local throttling phenomenon at this position, and the temperature rapidly drops, causing condensation or frost.

3. Processing method:

1) If your water chiller frost on the inlet of the filter, and the intermittent airflow sound is heard, use the small wrench to gently tap the filter body, the airflow sound changes, and the filter and the capillary front frost layer melt, the filter can be judged.

The imported filter is clogged.

At this point should:

1 Remove the capillary, clean the filter and blow-dry, and reinstall. Or replace the filter

2 The vacuum is applied and the refrigerant is added to the specified amount.

Chapter 9: Maintenance of water chiller

Tips for maintenance of water chillers

1. If it is not an emergency, do not turn off the water chiller by cutting off the main power.

2. When the water chiller malfunctions and stops, first turn off the main power switch of the machine (the alarm light will go out) and then check the cause of the fault.

But do not force the water chiller to boot before the fault is eliminated.

3. To extend the life of the water chiller and prevent the occurrence of safety accidents, regular inspections must be carried out.

4. The water used in the water chiller should be treated with water.

The high alkaline water quality will intensify the corrosion of the copper tube and reduce the service life of the heat exchanger. The PH value of the water used is in the range of 7.0-8.5.

5. Keep the water-cooled chiller machine room dry, clean, and well ventilated.

6. The daily operation, management, and maintenance of the water chiller must be performed by professionals with professional skills.

(It is dangerous to disassemble or inspect when the water chiller is running, please be careful)

During the normal operation of water chillers, it is unavoidable that dirt or other impurities affect the refrigeration effect.

Therefore, to prolong the service life of water chillers and make the refrigeration effect more stable, regular maintenance should be done to ensure the operation quality of water chillers and improve production efficiency.

Check regularly whether the voltage and current of water chillers are stable and the sound of a compressor is normal.

If it is a semi-closed compressor, check regularly the oil quantity. Normally, it should be more than 2/3 of the window.

When the water chiller works normally, the voltage is 380V and the current is normal in the range of 11A-15A.

Regularly check whether the refrigerant of the water chiller has leakage: refer to the parameters indicated on the high and low-pressure gauges on the front panel of the main unit.

According to the temperature (winter, summer) temperature changes, the water chiller pressure display is also different.

When the water chiller is working normally, the high pressure shows 11-17kg, and the low pressure shows 3.5kg-5kg.

Check whether the water-cooled chiller is normal, whether the cooling tower fan and the sprinkler shaft are working well, and whether the water replenishment of the water tank of the water chiller is normal.

Water chillers should be replaced with new water for 3 months. If it cannot be replaced, add a rust remover.

All Water chillers should be cleaned once every six months and cleaned once a year. The main cleaning parts include: cooling tower, cooling water pipe, and condenser to ensure better cooling.

When water chillers are not used for a long time, circuit switches such as pumps, compressors, and the general power supply of cooling towers should be switched off in time.

Water chillers need to be connected with cooling towers and circulating pumps to achieve a refrigeration effect.

To ensure the quality of circulating water, Y-type filters can be installed at the source of water, and algaecide and scale remover can be added to the cooling towers to avoid impurities entering the pipeline affecting the operation of the unit.

Cleaning Method of Condenser Pipeline

Cut off the power switch.
Close the cooling water inlet and outlet ball valve.
Remove the front panel of the water chiller.
Remove the fixing screw and remove the round cover plate. A copper pipe can be seen. Please use a copper brush to clear it back and forth.

Filling the refrigerant

Unscrew the lid of the liquid thimble valve and connect the air tube of the vacuum pump to the liquid thimble valve for vacuuming.

This process takes about 1~3 hours.

After the vacuum is completed, the gas pipe of the refrigerant tank is connected to the liquid addition ejector valve, and the refrigerant is added to the return gas pipe.

Monitor the electronic weighing change and stop the refrigerant when filling the rated weight. (It is strictly forbidden to charge liquid refrigerant in the on-state).

Under the state of being turned on, the high-pressure gauge shows the pressure: 13~15bar; the pressure gauge of the low-pressure gauge shows the pressure is about 3~5bar.

The water chiller adopts a shell-type external condenser. After a long time of use, the inside of the heat transfer tube accumulates scale, which affects the heat transfer effect.

The condenser should be cleaned regularly to keep the water chiller in good working performance.

If the cooling water has been treated with clean water, it is recommended to use the hydrogen peroxide to sterilize the algae, and then wash the ear with a high-pressure water gun to check the water.

After pickling, it must be passivated, and a passivating agent can be purchased for related treatment.

Water Chiller Installatioin and Maintenance

Water Chiller Installation and Maintenances

When the water chiller is not used or stored in an environment below 0 °C, the pipeline is disconnected, the front end of the machine is raised, and the water wrapped in the frost condenser is discharged.

The shell-and-tube evaporator of the ice water chiller is used for a long time.

The outer side of the heat-transfer tube accumulates scale, which affects the heat transfer effect. Celebrate the cleaning of the evaporator regularly to keep the machine in good working condition.

The evaporator is cleaned by washing the ice cream condenser. The scale is discharged from the drain.

Conclusion

At  TopChiller, we design and manufacture our water chillers to overcome your most challenging problems. Our water chillers are no exception.

We are always providing our customers with innovative solutions to their industrial processing applications, providing unparalleled technical knowledge, design expertise, and exceptional service.

TopChiller in Philippines
TopChiller in the Philippines

TopChiller is available 24/7, so we are ready to assist you whenever you need us!

Whether you buy a water chiller or you are planning to build a new plant, here is the right choice for you. We will provide you with the most suitable service.

TopChiller will unconditionally provide you with the most professional advice to help you choose the most suitable water chiller solution for your own.

Here is a variety of high-quality water chillers for your choice, and arrange professional technical personnel to train and install water chiller, and provide free advice on troubleshooting to guide your technical personnel on how to supervise and inspect water chiller.

As the most professional water chiller supplier, you buy not only the selected equipment but also lifetime service for customers.

As long as you want, we will become your partner to help you start your water chiller business.

Water Chiller-The Ultimate FAQ Guide by TopChiller

Regardless of whatever industry you are in, there is a decent possibility that your organization depends on your everyday tasks.

If your daily operations require chilled water, a Water Chiller is exactly what you need.

We are sure about Water Chiller is playing more and more role for your industrial applications.

The Water Chiller will surely meet your expectations by performing efficiently and effectively.

This guide contains every detail that can help you to guide about Water Chiller.

Let’s start it.

What is a Water Chiller?

A Water Chiller is also known as an industrial Water Chiller, chilled water plants or chilled water systems, air cooling pieces of equipment.

These produce chilled water and are reasonable for various industrial and business applications.

Many producers offer a unique and good variety of Water Chiller that suits a wide scope of industries and businesses.

Water Chiller works similarly to air chiller yet requires two stages to finish the exchange of heat.

In the beginning, in the Water Chiller heat enters the condenser water from the refrigerant vapor.

Then in the Water Chiller, the warm and hot condenser water is then forced to the cooling tower, where the heat from the procedure is at last passed out into the air.

The Water Chiller removes heat from a load and moves it to the climate, utilizing a refrigeration system.

This heat-shifting Water Chiller is the best cooling machine in power plants.

Water Chiller has been just a system that has ethylene + water or water reservoir and circulation segments.

The cooling liquid is circled from the reservoir to the cooling equipment in the Water Chiller.

Water Chiller System has a cooling tower, still, they include higher proficiency, effectiveness, and efficiency than the air chiller.

A Water Chiller is more productive and efficient because they condense depending upon the ambient temperature bulb temperature, which is lower than the surrounding dry bulb temperature.

The lower a Water Chiller gathers; the more productive and effective is.

The Water Chiller system has a few components including:

Cooling towers, Condenser water pumps, Make-up water pumps, Chillers, and TES reservoirs. The water-cooling procedure is commonly finished.

It is finished with circle chilling from a Water Chiller to process and consequently offers constant or discontinuous cooling to any liquid-cooled processor-sensitive instruments or machines.

Water Chiller

Water Chiller

What are the Features of Water Chiller?

The Water Chiller has several features which can be highlighted before the time of choosing the best option for business or personal use.

It contains stainless steel, a brazed plate evaporator or shell, and a tube barrel (counsel processing plant explicit data on your model), and a Microprocessor Chip Controller.

It also contains a mechanical obligation system procedure pump, scroll compressor crankcase warmer, condenser (s): coaxial steel copper tube, suction gatherer.

Water Chiller also assists or helps in Water flow changing as a feature of Hot gas by-pass limit control.

Water Chiller assists in Liquid line drier, sight glass, solenoid, TEV 24V control transformer and contains compressor engine contractor, control circuit intertwining, “Hard beginning pack” (Single-stage units as it were).

The Water Chiller has painted electrifies sheet metal cabinet models with brazed plate evaporator, 1/2″ protection of all water and refrigerant lines, the full refrigerant charge from the processing plant.

Water Chiller assists in automated industrial facility run tests under high load conditions.

It has unsoiled steel stockpiling tank with ½” protection, an intertwined unsoiled steel re-circulation pump for tank activity with a ball valve, and a cleanable sifter.

Water Chiller System supports tank pressure relief valve, vent, and drain connections.

It is manufactured and made to meet the best expectations and incorporate all the features you require for any mechanical or industrial application.

A Water Chiller is an investment that is manufactured or made to last: a primary steel outline that protects the from massive damage.

And removable steel boards that permit access for routine assessment and upkeep or maintenance. The tempered steel pumps are resistant to consumption.

These diffusive coursing pumps have high-proficiency impellers, centerline connections, and mechanical seals.

With bronze valves and enduring or long-lasting, completely protected brazed copper inside Water Chiller channeling all through, you will not need to stress over ferrous metals rusting or plastic getting weak inside Water Chiller.

Regardless of its solidness, it has a smaller design with casters for simple moves.

Water Chiller Cooling Tower

Water Chiller Cooling Tower

How does a Water Chiller Functions?

A Water Chiller deals with the guideline of vapor pressure or vapor absorption.

The Water Chiller gives a persistent progression or flow of coolant to the cold side at an ideal temperature of about 50°F (10°C).

The coolant is then pumped through the interaction, extricating heat out of one region of a facility (e.g., engine, process equipment, etc.) as it flows back to the return side of the Water Chiller System.

A Water Chiller utilizes a vapor pressure mechanical refrigeration system that connects with the interaction through a gadget or device called an evaporator.

Refrigerant circulates through an evaporator, compressor, condenser, and extension device of a Water Chiller.

A thermodynamic interaction happens in each of the above parts of a Water Chiller.

The evaporator functions as a heat exchanger with the end goal that heat caught by the process coolant flow moves to the refrigerant.

As the heat movement happens inside the Water Chiller, the refrigerant vanishes, transforming from a low-pressure fluid vapor, while the temperature of the interaction coolant decreases.

The refrigerant at that point flows to a compressor, which plays out various capacities.

To start with, it reduces refrigerant from the evaporator and guarantees that the pressure in the evaporator stays sufficiently low to absorb heat at the right rate.

Second, it brings the pressure up inactive refrigerant vapor to guarantee that its temperature stays sufficiently high to deliver heat when it arrives at the condenser.

The refrigerant returns a liquid state at the condenser. The inactive heat surrendered as the refrigerant changes from a gas to fluid is diverted from the climate by a cooling medium (water).

The Water Chiller highlights a water condenser connected to a cooling tower.

It has usually been utilized for medium and enormous or large installations or establishments that have an adequate water supply.

It can deliver more consistent execution for business and mechanical cooling because of the overall freedom to changes in the surrounding temperature.

Water Chiller range in size from little 20-ton limit models to a few thousand-ton models that cool the world’s biggest offices, for example, air terminals, shopping centers, and different offices.

A typical Water Chiller utilizes recycling condenser water from a cooling tower to gather the refrigerant.

A Water Chiller contains a refrigerant reliant on the entering condenser water temperature (and flow rate), which capacities according to the surrounding wet-bulb temperature.

Since the wet-bulb temperature is consistently lower than the dry-bulb temperature, the refrigerant condensing temperature (and pressure) in a Water Chiller can regularly work altogether lower than an air chiller.

Subsequently, it can work all the more productive.

Water Chiller commonly designed inside a climate, protection from the components.

Moreover, it can offer a more extended life expectancy.

Water Chiller regularly addresses the choice for bigger installation.

The extra cooling tower system will require extra installation cost and support or maintenance when contrasted with the air chiller.

Water Chiller Working

Water Chiller Working

What are the Advantages of Using Water Chiller for your Application?

Firstly, Water Chiller is high in productivity and has partial load energy effectiveness up to 6.1, step control is applied as default.

A Water Chiller is high proficiency smaller semi-airtight screw compressor, low pressure proportion dodges overpressure or compression, and short compression.

Design condition has been advanced to be as close as concerning the genuine application, execution to some extent load expanded essence.

It also has a high productivity evaporator, fully counter flow heat exchanger, high proficiency.

Water Chiller has exact control by high exactness and quick reacting electronic expansion valve, changed with compressor simultaneously.

It starts consistently, avoids the refrigerant (liquid) from scattering into the compressor.

Improved refrigerant line configuration, zero pressure drop (P=0kPa) ball valve increment productivity, and execution.

It also controls high exactness temperature sensor (+/ – 0.3oC), working reach 20~150oC.

Superheat degree controls SCH, quick reacting on the refrigerant side, more precise and adopt “fluffy control” rule to control the compressor limit, yield-based real interest, accordingly, lessening power utilization.

A Water Chiller is an environment-friendly refrigerant: R134a, ODP=0, GWP=0.29, no harm to the ozone layer.

Water Chiller assists by Less refrigerant charge, Less GWP impact, greater climate-friendly, for example, WLWC-520C3A, refrigerant charge=172kg, and the overwhelmed type of the same model, refrigerant charge=340kg.

Moreover, it makes low running noise and lowers contrast with ordinary items or products with upgraded system plans and noise reduction measures.

Water Chiller makes low noise or sound, compact screw compressor (mechanical and electromagnetic sound).

Water Chiller has high execution or performance noise protection (Armaflex) for key noise points extra noise reduction can be accomplished with optional noise decreasing gadgets.

It has a power confinement switch for safety improvement and extra safety with inbuilt power assurance.

The Water Chiller has monitor equipment, insurance, and protection class IP 30 can assist in the quick release of system pressure by a 1-inch safety valve.

Besides, the Water Chiller is easy and simple for installation, upkeep or maintenance, and service. It has one side water pipe connection or linkage, and Water Chiller is simple for connecting and space-saving.

Water Chiller contains clamp-type pipe connection simple for linking and support also has a ball valve on the release line and refrigerant line, 1/4 circle from full open to full close, and turn limitation on both fully open and full close interaction, simple for support.

The Water Chiller contains easy to use HMI-sensitive LCD contact or touch screen regulator with great client experience and a simple admittance or access to a system running boundaries and running bends.

The Water Chiller has verifiable running records and failure records are stored up to 80 records. Approved admittance or access is incorporated.

The Weekly-timer function is incorporated in it. Self-Diagnostic and alarm alert capacity is incorporated as well and manual reset work is incorporated inside the Water Chiller.

Water Cooled Chiller

Compact Design Water Chiller 

Why do you Need a Water Chiller for your Application?

Having a Water Chiller is especially significant because it will in general warmth up quicker than a system that courses the supplement arrangement.

In case you are utilizing a channel and flood system, you may have to chill both the water and air keep up sound root zone temperatures, and avoid shock and for that water, the chiller is the best way to do it.

Numerous factors explain the reason why you need a Water Chiller as it can help you in many different ways.

Firstly, a Water Chiller burn-through or consumes over 10% less energy than an air chiller.

Secondly, it is less expensive or cheaper for a similar cooling capacity.

Thirdly, it has a more extended life expectancy.

Moreover, it is generally soothing and noiseless than the air chiller.

Furthermore, the Water Chiller gives a more reliable cooling performance.

It is more cost-effective than an air chiller in circumstances where a large cooling capacity is required.

Water Chiller is Widely Used in the Manufacturing Industry

Water Chiller is Widely Used in the Manufacturing Industry

What are the Types of Water Chiller?

There are various sorts of Water Chiller, and this guide can help you locate the correct one.

Indeed, offer to help keep your investment to a minimum.

By managing the plant, you can talk with specialists who can assist you with getting the correct Water Chiller for your necessities.

You will not need to stress over overspending or not getting the highlights you need.

Explosion Proof Water Chiller

Explosion Proof Water Chiller

What is the Difference between Water Chiller and Air Chiller?

Water Chiller System has a cooling tower; hence they highlight higher proficiency than an air chiller.

A Water Chiller is more effective because they consolidate, depending upon the encompassing temperature bulb temperature, which is lower than the surrounding dry bulb temperature.

The lower a Water Chiller consolidates; the more productive it is.

This Water Chiller system has a few fundamental segments including:

  • Cooling towers
  • Condenser water pumps
  • Make-up water pumps
  • Chillers
  • TES reservoirs

A few clients may prefer or choose to Water Chiller because of the more modest size they involve when contrasted with air chiller.

This Water Chiller additionally includes higher proficiency and lasts more than the referenced other option.

The individuals who might want the equipment to be set inside may discover the Water Chiller machine alluring and desirable.

  • Evaporator

The job of the evaporator is to create chilled water. The device delivers the water at about 6°C (42.8°F) and pushes it all through the facility with the assistance of a pump.

Inside a Water Chiller, a network of lines or pipes passes the chilled water through each fundamental segment of the structure of the building.

In the wake of trading coldness to room air, which blows across the air handling units (AHU’s) and fans coil units (FCU’s), the water is currently hotter and warmer at about 12°C (53.6°F).

It gets back to the evaporator where the refrigerant absorbs the undesirable heat and makes it move towards the condenser.

  • Condenser

A refrigerant inside the Water Chiller brings undesirable heat from the evaporator and goes through the condenser.

There is another circle connected to the condenser-the condenser water circle, which is between the cooling tower and the condenser.

After entering the condenser at about 27°C (80.6°F), the water leaves at 32°C (89.6°F) and heads to the cooling tower.

Note that at no time do the refrigerant and the condenser contact straightforwardly. Heat trade is just through a line or pipe wall.

The condenser water, with the undesirable heat, goes to the cooling tower for additional heat dismissal.

  • Cooling Towers

This is the place where the undesirable heat in an office ends up. A large fan takes care of the unit with air.

The air meets with the approaching condenser water. From the immediate contact, the condenser water loses heat to the air.

Presently, contrast it with the air chiller talked beneath.

Where style and natural conditions or water access limitations exist, the air chiller might be applied.

Both air and Water Chiller rely upon airflow as a method for heat movement.

The thing that matters is that the Water Chiller or rather the cooling towers utilize a moist airflow (ambient airflow + water spray) while the air chiller utilizes a flow of surrounding air.

Typically, a Water Chiller is less expensive and more productive, with the impediment of high-water utilization.

Air Chiller

Air Chiller

What are the Applications of Water Chiller?

The norm, standards, and custom units have been utilized and Water Chiller is made for applications altogether enterprises and industries, notably:

Water Chiller can be used in air compressor cooling, presses, injection molding, extrusion, and blow molding.

Water Chiller can also be used in laser cutting, welding, and optics.

Not just these, It can be used in clinical, substance and pharmaceutical, breweries, wineries, food processing.

Other than that, it is used in jacketed vessels, research facilities, and laboratories.

Lastly, it is used in machine tools, printers, and water-driven Cooling, and many more.

What Factors should you consider Before Choosing a Water Chiller for your Application?

Other significant Water Chiller details incorporate the voltage needed for the activity, the related pipe drive and flow rate, the water size, and the evaporator type.

  • Power

Various nations and areas have various norms for mechanical power related to Water Chiller, the basic force supplies are 208-230V, 380-420V,440-480V,50Hz or 60Hz, 3phase.

  • Water Pump

At the point when you choose the limit/weight of the Water Chiller, this guide will suggest to you the appropriate power horse of the pipe.

  • Connection Size

This generally relies upon the water flow rate, the higher the greater.

On the off chance that you need your new Water Chiller to coordinate your old lines and pipes.

  • Refrigerant

R22, R410A, R407C, R404A, R134A is discretionary or optional decision.

R22: great cooling impact, however, R22 is viewed as a groundbreaking ozone-depleting substance, so it is illegal in many nations.

R410A: eco-accommodating and friendly, R-410A has supplanted R-22 as the favored refrigerant for use in private and business forced air conditioners in Japan, Europe, and the United States.

R-410A works at higher pressures than different refrigerants.

R407C: a decent swap for R22, great cooling impact.

R404A: reasonable for application which requires low temperature (below – 30°c).

R134A: a non-flammable gas utilized essentially as a “high-temperature” refrigerant, reasonable for Water Chiller working at a high surrounding temperature.

  • Evaporator Choose

Water Chiller has two general kinds of the evaporator.

Shell and cylinder type evaporator, which requires an extra water support tank to use (not fundamentally however energetically suggested).

Water Chiller Refrigerant

Water Chiller Refrigerant

How to Choose the Right Cooling Capacity for a Water Chiller for your Application?

Perhaps the most frequently asked about Water Chiller determinations is how to decide the size/weight. Let us see underneath the equation.

Compute Temperature Differential = Incoming Water Temperature (°c) – Required Chilled Water Temperature.

Compute the water flow rate that you need each hour (m³/hour).

Compute huge loads of cooling limit = Water Flow Rate into Temperature Differential

Divided by 0.86 divided by 3.517.

Oversize the Water Chiller by 20% Ideal Size in Tons = Ton x 1.2.

You have the ideal size for your requirements.

For instance, what size of Water Chiller is needed to cool 5m³ water from 25°c to 15 °c in 60 minutes?

Temperature Differential = 25°c-15°c=10°c.

Water Flow Rate = 5 m³/hour.

Ton Capacity = 5 x 10 ÷ 0.86 ÷ 3.517 = 16.53 Ton.

Oversize the Water Chiller = 16.53 x 1.2 = 19.84 Ton.

A 19.84 Tons Water Chiller is required.

What are the Instructions for Installing Water Chiller?

  • Uncrating and checking Unit for Damage:

Eliminate packing material and analyze unit for delivery damages on Water Chiller.

The consignee is liable for making a guarantee to the transportation specialist and any harm ought to be accounted for right away.

While moving your Water Chiller, it can be folded into position.

However, if it is important to lift the unit, this ought to be finished with the base casing as it were.

If you should utilize lifting links or chains, be mindful so as not to harm parts controls or lines.

  • Install Water Chiller:

Remove packing and find the Water Chiller position.

Building development should take into account sufficient wind current on the sides, top, and back of the Water Chiller.

  • Make a water supply connection:

Make connections between Water Chiller and process supply line.

Intel port and the outlet port are set apart on the Water Chiller. Turn the water supply and flush the line completely, likewise, check for spills.

All Water Chiller in/outlines to be protected to keep up or maintain legitimate heat adjustment and keep the loss of heat from the outlet.

Fill the water in the tank as required and deliver the isolated space in the pipe pull zone.

  • Electrical Supply:

The power and Control board is completely encased and enclosed, dustproof complete with all-important exchanging, control, and safety gadgets.

Make a separate electrical connection for the Water Chiller for example 230V or 415V. Additionally, guarantee that a legitimate electric connection to the Water Chiller (body earth).

  • Water flow:

If it is not too much trouble, check the water flow rate and working pressure of the water before supply to the Water Chiller. Likewise, guarantee the great nature of the water supply.

How to Maintain your Water Chiller?

  • Several factors should consider for the maintenance of your Water Chiller.
  • Try not to surpass Water Chiller evaluated configuration flow and inner temperature to stay away from poor cooling.
  • Keep the Water Chiller in a spotless and ventilated spot. There ought not to be any residue or dust and other toxins which may block the condenser unit.
  • Try not to change/alter any of the segments in the Water Chiller. They are plant set and ought to be changed exclusively by the approved assistance people.
  • Do give a stabilizer if your voltage varies excessively.
  • Regularly examine for refrigerant leakage.
  • Check compressor working pressure and oil level.
  • Check every electrical starter, contractor, and transfer.
  • The pump and machine connection ought to be checked consistently for spills or leakage.
  • The pump engine ought to be checked routinely for stopping air channels, prompting overheating.
  • Pump and fan orientation ought to be checked for noise and grease.
  • Oil bearing just as regularly as maker indicates.
  • Water Chiller and water tank ought to be perfect.
  • The tank may be depleted occasionally to supplant system water and clean debris and jetsam from the tank.
  • Dirty water can cause excessive heat exchangers and pump seal wear.

Water Chiller maintenance

Water Chiller Maintenance

How to Increase the Working Efficiency of your Water Chiller?

Water Chiller costs burn-through a generous piece of your building’s utility bills.

What measures would it be a good idea for one to take to get energy reserve funds through the maximal effectiveness of your Water Chiller system?

Assess and clean condenser coil.

Heat movement largely affects the Water Chiller system and stays crucial to creating effective chiller activity.

Routine upkeep and maintenance ought to investigate condenser coils for obstructing and free air sections.

Keep up and maintain the refrigerant charge. A Water Chiller’s cooling remainder relies upon proper refrigerant levels in the system.

Keeping up and maintaining the appropriate refrigerant charge can enormously affect the energy effectiveness by diminishing cooling costs by almost 5-10%.

The advancement of the general Water Chiller plant should be performed comprehensively.

Different changes focusing on ideal chilled water set focus, Water Chiller sequencing and load adjusting, peak demand management, and so on must be performed with operational information.

It can give the tools for such improvement by giving ongoing observation of force utilization from each piece of the chiller plant.

FAQ of Water Chiller

  1. Which Water is used in Water Chiller?

Water Chiller commonly uses deionized water (DI). It resists the flow of electric current. Some applications use water-glycol to prevent freezing and bacterial growth.

  1. What Additional Components are required for Water Chiller as Compared to Air Chiller?

As compared to Air Chiller, a Water Chiller requires a high-quality cooling tower and a cooling pump to perform together for proper circulation of water in the process.

  1. What are the Low and High-Temperature Ranges of a Water Chiller?

A Water Chiller is capable of controlling the high-temperature range between 5 degrees Celsius to 35 degrees Celsius.

It can control the low temperature between zero degrees Celsius to -40 degrees Celsius.

  1. How a Water Chiller is Different from an Air Chiller?

The main difference between a Water Chiller and an air chiller is of condensers they use for heat dissipation processes.

A Water Chiller uses water as a source for heat dissipation while an air chiller uses air for this purpose.

  1. How many Components does Water Chiller Have?

This Water Chiller system has numerous essential components including:

  • Cooling towers
  • Condenser water pumps
  • Make-up water pumps
  • Chillers
  • TES reservoirs
  1. Does Air Chiller Consume more Energy than Water Chiller?

A Water Chiller consumes more than 10% less energy than an Air Chiller.

  1. How do you choose between Air Chiller and Water Chiller?

The cooling capacity is the main guideline to choose between both Air Chiller and Water Chiller.

  1. How to Optimize the Performance of your Water Chiller?

Assess and keep a regular check on your Water Chiller working activity.

  1. How much will it cost to maintain your Water Chiller?

It depends on what type of maintenance your Water Chiller needs.

  1. How to Prevent Leakage in your Water Chiller?

It will require regular checking and assessment to prevent and avoid leakage.

100% Quality Tested Water Chiller

100% Quality Tested Water Chiller

Get TopChiller Quotation

Scroll to Top