Product

55KW -10C water cooled glycol water chiller for chemical industry use

Minimum Order : 1 , Pieces

Water-cooled Glycol/Low Temperature Industrial Chiller

General Description


HTLT-A air cooled low temperature industrial chiller is widely applied in small-medium scale low temperature industrial cooling, such as chemical industry, pharmacy, food industry, etc. 


Water cooled industrial chiller works with a cooling tower. It requires less installation room, and could be located in a relevant close space.




Design features


-Water temperature range -35ºC to 20ºC.   

-Danfoss/Copeland scroll compressor. 

-For temperature below -15℃, semi-hermetic piston type compressor will be adopted.

-Shell and tube evaporator, plate type for option.

-Shell and tube condenser.

-Microcomputer control system offering accurate temperature stability within ±1ºC.
-Large flow volume centrifugal pump, higher pressure available on request.
-Multi-protection devices to make sure the chiller and the equipment running safety.
-Schneider electrical components.
-Danfoss/Emerson thermal components.




Unit Safety Protection


-Compressor inner protection
-Over current protection
-High/low pressure protection
-Over temperature protection 
-Flow switch
-Phase sequence/phase missing protection
-Low coolant level protection
-Anti freezing protection 
-Exhaust overheat protection

Product parameters

Model[HTLT-***]

3W

5W

6W

8W

10W

12W

15W

20WD

25WD

30WD

40W

Nominal cooling

capacity

-10

kw

4.5

7.7

9.1

11.7

16.1

19.1

23.3

32.2

38.2

46.6

62.5

-20

2.7

4.1

5.3

8.1

9.8

10.6

13.6

20.4

25

29.4

38.5

-30

1.31

2.1

2.8

4.3

4.9

5.6

7.9

11.2

13.7

16.1

21.2

-35

0.85

1.3

1.9

2.8

3.3

3.8

5.3

7.8

9.4

13.8

17.8

Condenser

Type

 

Shell and tube type

Cooling water

flow

-10

m3/h

1

1.7

2.03

2.62

3.6

4.27

5.2

7.23

8.54

10.4

14

-20

0.61

0.92

1.09

1.82

2.03

2.37

3.04

4.56

5.6

6.58

8.61

-30

0.31

0.49

0.65

1

1.14

1.3

1.84

2.61

3.19

3.74

4.93

-35

0.2

0.31

0.44

0.65

0.77

0.89

1.23

1.81

2.18

3.2

4.13

Pipe connection

inch

1-1/2

1-1/2

1-1/2

1-1/2

1-1/2

1-1/2

2

2

2-1/2

3

3

Evaporator

Type 

Shell and tube / SS plate heat exchanger

Coolant 

volume

-10

m3/h

0.77

1.33

1.56

2.01

2.77

3.28

4

5.56

6.57

8.01

10.75

-20

0.47

0.71

0.91

1.4

1.69

1.82

2.34

3.51

4.3

5.06

6.62

-30

0.23

0.36

0.48

0.74

0.84

0.96

1.36

1.93

2.36

2.77

3.65

-35

0.15

0.22

0.33

0.48

0.57

0.65

0.92

1.34

1.62

2.37